Digester Gas Monitor Operators Manual Supported Modbus Functions 75
Registers 40025 - 40027
The 6 bytes (characters) in these registers contain the channel gas reading in ASCII
characters.
Registers 40028 - 40029
The 4 bytes (characters) in registers 40028 and 40029 represent the channel gas units in
ASCII characters.
Registers 40030 - 40043, Channel 3 Information
Register 40030
Table 18 below shows the information in register 40030.
Registers 40031 & 40032
The 32 bits in registers 40031 and 40032 contain the channel 2 numerical reading in
single precision floating point IEEE format.
Register 40033
The 16 bits in register 40033 contain the channel 2 numerical reading in integer form
omitting the sign (+ or -) and the decimal point.
Register 40034
Table 19 below shows the information in register 40034.
Table 18: Register 40030
Channel Operational State
(MS-Byte)
Channel Status Bits
(LS-Byte)
0 = (this code is not used)
1 = Standby
2 = Normal Operation
•3 = Warm Up
•4 = Fail
•5 = Post-Calibration
6 = Low Power
Bit-7 (msb) = Relay-1 (1 = energized)
Bit-6 = Relay-2 (1 = energized)
Bit-5 = (this bit is not used)
Bit-4 = Alarm-1 (1 = asserted)
Bit-3 = Alarm-2 (1 = asserted)
Bit-2 = Alarm-3 (1 = asserted)
Bits[1:0] = Channel Usage Code
[00] = Not Used
[01] = Standby
[10] = Active
[11] = unused code
Table 19: Register 40034
Channel Reading Sign (+/-)
(MS-Byte)
Channel Decimal Point Position
(LS-Byte)
0 = Positive (+)
1 = Negative (-)
•0 = No Decimal Point
1 = .x
2 = .xx
3 = .xxx