RKI Instruments, Inc. • 1855 Whipple Rd. • Hayward, CA 94544 • (510) 441-5656
Model GD-K11D
Operator’s Manual
Part Number: 71-0029RK
Edition: First
Released: August 1997
Vue de la page 0
1 2 3 4 5 6 ... 25 26

Résumé du contenu

Page 1 - Model GD-K11D

RKI Instruments, Inc. • 1855 Whipple Rd. • Hayward, CA 94544 • (510) 441-5656 Model GD-K11D Operator’s Manual Part Number: 71-0029RKEdition: FirstR

Page 2 - Warranty

6 • Description Model GD-K11D Operator’s Manual Status lights The display board includes five status lights. Table 3 lists each light and its functi

Page 3 - Table of Contents

Model GD-K11D Operator’s Manual Description • 7 Adjustment potentiometers The display board includes two potentiometers, which extend from the bott

Page 4

8 • Installation Model GD-K11D Operator’s Manual Installation This section describes how to install the Model GD-K11D at the monitoring site. This

Page 5 - Specifications

Model GD-K11D Operator’s Manual Installation • 9 2. Use two screws through the slot cutouts at the top of the housing to secure the housing to a ve

Page 6

10 • Installation Model GD-K11D Operator’s Manual Connecting AC power 1. Loosen the thumbscrew at the top of the housing.2. Rotate the housing cove

Page 7 - Description

Model GD-K11D Operator’s Manual Start Up • 11 Start Up This section describes procedures to start up the Model GD-K11D and place the Model GD-K11D

Page 8 - Flow System

12 • Start Up Model GD-K11D Operator’s Manual6. Press the MODE button.The ZERO light turns off, and 3. appears on the display screen.NOTE: The purpo

Page 9 - Detection System

Model GD-K11D Operator’s Manual Operation • 13OperationThis section describes procedures to display the peak reading, and to adjust the alarm point,

Page 10

14 • Operation Model GD-K11D Operator’s Manual3. Adjust the INT switch to the “2” position.The current alarm point appears on the display screen, and

Page 11

Model GD-K11D Operator’s Manual Operation • 15Adjusting the Alarm TypeYou can program the Model GD-K11D’s alarm to activate on increasing readings or

Page 12 - Installation

ii • Warranty Model GD-K11D Operator’s Manual Warranty RKI Instruments, Inc., warranties gas alarm equipment manufactured by RKI and sold by RKI to

Page 13 - Wiring the Model GD-K11D

16 • Alarms Model GD-K11D Operator’s ManualAlarmsThis section describes the Model GD-K11D’s visual indications for normal, alarm, and fail conditions

Page 14

Model GD-K11D Operator’s Manual Maintenance • 17MaintenanceThis section describes maintenance procedures for the Model GD-K11D. It includes preventiv

Page 15 - Start Up

18 • Maintenance Model GD-K11D Operator’s ManualTroubleshootingThe troubleshooting table describes error messages, symptoms, probable causes, and rec

Page 16

Model GD-K11D Operator’s Manual Maintenance • 194. Pull the metal restraining bracket that secures the sensor in the housing away from the sensor, th

Page 17 - Operation

20 • Maintenance Model GD-K11D Operator’s Manual4. Use the ZERO potentiometer to adjust the display reading to zero.5. Press the MODE button.The ZERO

Page 18 - Adjusting the Alarm Delay

Model GD-K11D Operator’s Manual Calibration • 21CalibrationThis section describes how to calibrate the Model GD-K11D. It includes procedures to prepa

Page 19 - Adjusting the Alarm Type

22 • Calibration Model GD-K11D Operator’s ManualSetting the Response (Span) Reading1. Adjust the INT switch to the “1” position. The INT switch is th

Page 20 - Alarm Indications

Model GD-K11D Operator’s Manual Table of Contents • iii Table of Contents Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .

Page 21 - Maintenance

iv Model GD-K11D Operator’s Manual

Page 22 - Replacing Components

Model GD-K11D Operator’s Manual Overview • 1 Overview The Model GD-K11D sample-draw transmitter is a single-point, fixed-instrument. It continuously

Page 23 - ∇ button to display 3

2 • Specifications Model GD-K11D Operator’s Manual Table 2 lists the gases that the Model GD-K11D is capable of detecting. Table 2 also lists the d

Page 24

Model GD-K11D Operator’s Manual Description • 3 Description This section describes the components of the Model GD-K11D. The Model GD-K11D consists

Page 25 - Calibration

4 • Description Model GD-K11D Operator’s Manual Electrical System The Model GD-K11D’s electrical system consists of the terminal strip, power switc

Page 26 - Returning to Normal Operation

Model GD-K11D Operator’s Manual Description • 5 Detection System The Model GD-K11D’s detection system consists of the sensor, lithium battery, ampl